25 | On 11/15/2023, at approximately 3:55PM, Licensing Program Analyst (LPA) Jonathan Tse conducted an unannounced case management visit regarding an Action Level Exceedance (ALE) due to lead in the Child Care Center's water. LPA was granted entry to the facility by Site Manager, Paul Biggs. LPA explained the purpose of the visit. Present during the visit were 1 staff and 1 infant. The facility is in compliance with staff-child ratios.
LPA discussed the new Assembly Bill (AB) 2370, Chapter 676, Statutes of 2018 requires the Lead Testing of water in the Child Care Center with the site director during the inspection. All Child Care Centers that are located in buildings constructed before January 1, 2010, must have their water tested and post the results by January 1, 2023, and every 5 years after the date of the first testing. The facility initially tested its water for lead on 11/9/2022 and was in compliance with the testing requirement.
The facility received the initial ALE report from the Vendor on 11/17/2022. Test results for one fixture in this facility exceeded a higher level of parts per billion (ppb) allowed, 5.5 ppb, fixture E(6.2). The fixture is a faucet in the infant classroom. Per Director, the facility stopped using the faucet and the adjacent water fixture. The facility provided water from fixtures that did not have any ALEs. The facility retested on 1/31/2023 and received the second ALE report from the Vendor on 2/6/2023, with fixture E being re-labeled as fixture A. Fixture A is now at 3.4ppb, under the threshold for an ALE. All other fixtures tested below the threshold and are in compliance with the Written Directives detailed in PIN 21-21.1-CCP.
Per Written Directives 101700.3(b)(2), licensees shall maintain a lead value at or below 5ppb in all outlets subject to testing requirements for the health and safety of children in care. The Written Directives are included in HSC 1597.16, and are specific guidelines for facilities to adhere to regarding lead water testing. Due to updated guidance on the written directives in PIN 21-21.1-CCP, the facility will be cited for the ALE of fixture E. The deficiency will be cleared the same day of the visit because the fixtures have retested below the threshold. LPA advised that lead testing results and LIC forms 9275, 9276 and 999 should be posted.
This report was reviewed and signed by Site Manager, Paul Biggs. |