Deficiency Type
POC Due Date /
Section Number | DEFICIENCIES | PLAN OF CORRECTIONS(POCs) |
Type A
09/21/2021
Section Cited
CCR
87705(j) | 1
2
3
4
5
6
7 | Care of Persons with Dementia. The licensee shall have an auditory device or other staff alert feature to monitor exits, if exiting presents a hazard to any resident. This requirement was not met as evidenced by: | 1
2
3
4
5
6
7 | Administrator agrees to ensure all auditory alarms are functional and activated. An additional auditory alarm will be installed to the outside of the exterior door to the room for R-1. At the time of this visit all bedroom exterior doors have functional auditory alarms installed on the inside are functional |
 | 8
9
10
11
12
13
14 | Based on the observations of LPA's the alarm on the exit door was inoperable in Rm#6. Staff stated alarm had been in-op for a minimum of 1 week so staff disabled the alarm resulting in an immediate risk to the health & safety of residents in care. | 8
9
10
11
12
13
14 |  |
Type A
09/21/2021
Section Cited
CCR
87411(a) | 1
2
3
4
5
6
7 | Personnel Requirements - General: Facility personnel shall at all times be sufficient in numbers, and competent to provide the services necessary to meet resident needs. This requirement was not met as evidenced by: | 1
2
3
4
5
6
7 | Administrator agrees to ensure all auditory alarms are functional and activated. An additional auditory alarm will be installed to the outside of the exterior door to the room for R-1. At the time of this visit all bedroom exterior doors have functional auditory alarms installed on the inside are functional. There will be at |
 | 8
9
10
11
12
13
14 | Based on observations by LPA's and statements by Staff, R-1 was able to leave the facility without the knowledge of staff on duty indicating insufficient staffing resulting in an immediate risk to the health & safety of residents in care. | 8
9
10
11
12
13
14 | a minimum one awake staff at night. |