1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32 | It was reported that the facility did not have a functioning fire extinguisher, smoke detectors, or required fire doors. Today’s visit revealed that there was one (1) fire extinguisher on the premises that was fully charged and last serviced on 01/27/2026. Smoke detectors were tested and were not hardwired, with only two (2) out of eight (8) detectors functioning and testable. One (1) operational smoke detector was located in the middle of the facility, above the kitchen, and the other was in a resident’s room located at the front of the facility. Two (2) carbon monoxide detectors were tested and one (1) was operational. A double door located in the middle of the facility was observed as well as each resident bedroom door, and the facility did not have required fire doors.
The Licensee stated that upon approval of licensure, fire doors were not required, and the facility has not made any changes that would require fire doors. The LPA consulted with a Los Angeles Fire Department (LAFD) City Fire Inspector who confirmed that the facility required fire doors and hardwired smoke detectors due to the facility’s approved resident status. The facility was approved for five (5) non-ambulatory and one (1) bedridden, for a total of six (6) residents.
Based on interviews and observations, the preponderance of evidence standard has been met; therefore, the allegation is deemed SUBSTANTIATED at this time.
An immediate civil penalty in the amount of $500 was assessed for a violation of the facility’s fire clearance (Refer to LIC 421M). The Licensee was advised that failure to correct may result in additional civil penalties.
Pursuant to Title 22 CA Code of Regulations and/or the Health and Safety Code, the following deficiency was cited (Refer to 9099-D).
Exit interview conducted. A copy of the appeal rights and report was reviewed and provided. |