1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32 | Allegation: Staff did not ensure air conditioner was working properly
The allegation alleges the facility is not kept at a comfortable temperature and the air condition is not working properly.
During record review, LPA received and reviewed invoices from C&M Mechanical dated 05/29/2025, 07/09/2025, 07/25/2025, 08/12/2025, 08/15/2025, and 08/29/2025. During the visit conducted on 08/29/2025 the technician inspected all rooms with temperature complaints to verify the status of fan coils. The technician found no error codes on the AC units specified rooms. The technician observed that the fan coils in all rooms with temperature complaints were turned off at the thermostats. Additionally, the technician observed some of the rooms had open windows and blinds, contributing to the heat issue. During the visit on 08/12/2025, the technician observed the fan coil seemed closed due to pipe temperature not changing in rooms 207, 203, and 201. Room 101 had closed ports. The technician observed a loose not on ball valve. The technician tightened the nut and made sure the ball valves were opened. On 08/05/2025, 08/08/2025, and 08/12/2025 filters were changed, and the condenser coils were checked and cleaned. On 07/25/2025, the technician checked room 204 whose thermostat was set to off, when turned on, the thermostat setting was on heating. It was switched to cooling, then functioned properly. The technician checked Room 213 and observed the thermostat was on heating. It was switched to cooling and it functioned properly. On 07/09/2025, the technician checked room 213 and observed the thermostat was on heating. It was switched to cooling and it functioned properly. On 05/29/2025, room 107 had an error code. The technician changed the main PCB board, and the error cleared. In room 112 the motors were going bad. The technician changed the motor and the main PCB board for fan coil. On 05/06/2025, the technician checked the main units on the roofs. The technician observed one unit was not getting power due to the breaker not fully in the on position. The technician conducted a diagnostic and did not find any additional issues.
During the facility tour, LPA took the temperature of all common areas and eleven resident rooms. The following temperatures were recorded in the assisted living lobby the temperature measured 74.3-degrees, the dining room measured 73.6-degrees, the activity room measured 72.1-degrees, the first-floor hallways measured 75.3, 73.2, and 74.3-degrees, and the second-floor game room measured 75.6-degrees Fahrenheit. The following rooms temperature was measured in the assisted living, room 103 measured 75.5-degrees, room 108 measured 76.4, room 209 measured 77-degrees, room 215 measured 76.6-degrees, 235 measured 77.3-degrees, and room 242 measured 70.7-degrees Fahrenheit. The following temperatures were measured in the Memory Care Unit, the hallway measured 75.2-degrees, the |