Deficiency Type
POC Due Date /
Section Number | DEFICIENCIES | PLAN OF CORRECTIONS(POCs) |
Type A
06/10/2021
Section Cited
CCR
87705(j)
| 1
2
3
4
5
6
7 | 87705(j) Care of Persons with Dementia. The licensee shall have an auditory device or other staff alert feature to monitor exits, if exiting presents a hazard to any resident.
This requirement was not met by evidence of: | 1
2
3
4
5
6
7 | Administrator agrees provide proof of delayed egress door repairs/replacements, and conduct inservice training regarding testing the delayed egress system for all exits by POC due date. |
 | 8
9
10
11
12
13
14 | Based on observation at 10:59 am during the delayed egress door testing in the memory care unit, as a part of a complaint investigation it was observed the right door did not open after the delayed egress time of 15 seconds. In addition, the alarm did not sound off on that door. The left side door was operable. This poses an immediate health and safety risk. | 8
9
10
11
12
13
14 |  |
Type B
06/10/2021
Section Cited
HSC1569.33(i)(1)(2)
| 1
2
3
4
5
6
7 | 1569.33(i)(1)(2) Unannounced inspections; notification of deficiencies; compliance; reports. The department shall design, or cause to be designed, a poster that contains information on the appropriate reporting agency in case of a complaint or emergency.Each residential care facility for the elderly shall post this poster in the main entryway of its facility.
| 1
2
3
4
5
6
7 | Administrator agreed to post the required poster that contains information on the appropriate reporting agency in case of a complaint. Submit photographs as proof of correction. |
 | 8
9
10
11
12
13
14 | Based on physical plant observation with Health and Wellness Director a complaint poster with DSS/CCLD complaint phone number was not observed in the 1st and 2nd floor main entryway areas. | 8
9
10
11
12
13
14 |  |