1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32 | Staff stated that the hot water issue has been ongoing for approximately two – three weeks. Recently a solution has been implemented that when med-techs are notified by care staff that the water is not getting hot enough for showers, the med-techs then turn the hot water on in resident rooms at the end of each hallway, and after running the water for approximately 10-15 minutes it gets warm enough for showers. They state this is just a temporary solution and does not work for all showers. Staff also stated they can provide bed baths to residents but were not guided on where to access water warm enough to provide the bed baths.
The Maintenance Director stated that on 5/24/2026 a plumbing company was called out due to a shower valve that could not be shut off, while the plumber was there another shower valve with a similar issue was reported by staff. The plumber stated that the issue with both the shower valves in resident rooms were not functioning properly and were mixing cold water back into the hot water line adding to the primary hot water issue. Some of the shower valves have been replaced but as of today’s visit not all the shower valves have been tested ensuring they work properly. Additionally, the Administrator and Maintenance Director stated the boiler company returned yesterday 5/26/2026 to make temporary adjustments to the hot water system until a replacement tempering valve arrives which is on back order and may take four to six weeks to arrive.
A similar complaint was received in June 2025. Although the facility shows it is taking measures to fix the issue at the time of the complaints, there is evidence that shows it is recurring and impacts resident care. As of today’s visit, the hot water system is still not delivering consistent hot water within regulation temperatures to all resident rooms.
Regarding the water delivered to the kitchen and dishware sanitization, the water delivered to the faucets in the main kitchen, located outside the resident neighborhoods, bypasses the tempering valve allowing for water delivery hotter than 120°F. The faucets in the kitchen are labeled, as required by regulation, indicating they deliver hotter water. Per California Title 22 regulation, for residential care facilities for the elderly, the facility must ensure disinfection of dishes and utensils by one of two means; either by maintaining hot water at a minimum temperature of 170°F at the final rinse cycle of diswashing machines, or by an alternative comparable method such as the addition of a sanitation agent to the final rinse water. This facility uses a sanitizing agent called Aqua Pure, containing sodium hypochlorite, during the sanitization process of washing dishes and utensils.
(Continued on LIC9099-C)
|